| HA1600A -
Description
and Specifications |
|
Overview
The HA1600A is a fast, easy to use mains and harmonics
analyser with a large and high resolution graphical display, capable of
continuous real-time analysis.
The HA1600A is intended primarily as a dedicated harmonics and flicker analyser
for compliance quality measurements, but it can also be used as a general
purpose mains analyser.
The unit is available with range of power connectors to suit different national
standards.
A printer interface is included for record keeping and archiving, along with
both RS-232 and USB interfaces for PC connectivity.
High performance power analyser
The HA1600A is a high speed, high accuracy ac power analyser
for single phase loads of up to 16 amps RMS.
Dual power cables allow the supply to the load to be independent of the supply
to the instrument. The output to the load is via a front panel mounted
‘standard’ mains connector. A wide range of power connectors is available
including most national types.
The HA1600A can measure Watts, VA, Volts rms, Volts peak, Amps rms, Amps peak,
Crest factors, THD, Power factor, Frequency and Inrush current.
The large display can show multiple parameters simultaneously as well as
graphical representations of voltage and current waveforms.
Dual 16 bit Analog to Digital converters continuously sample both voltage and
current and give a wide dynamic range. A fast Digital Signal Processor gives the
performance needed for continuous real-time analysis of the data. Advanced
algorithms yield accurate results, using extended precision or floating point
arithmetic wherever necessary. |
|
Compliance-quality harmonics analyser
All electrical equipment sold within the EEC
must comply with legislation relating to the harmonics content
of the current waveform.
The HA1600A has been designed to make these measurements both
quick and simple. It measures harmonics from the 1st to the 40th
and updates the display in real time.
It is suitable for pre-compliance measurements using a normal
mains supply and is capable of full compliance measurements to
EN61000-3-2 in conjunction with a suitable power source such as
the AC1000A.
Support is provided for both the 1995 and 2000 editions of
EN61000-3-2. Capabilities include continuous monitoring of the
supply voltage, continuous automatic calculation of harmonic
limits, and timed test sequences with analysis of fluctuating
harmonics.
Compliance-quality flicker meter
The HA1600A can operate as a compliance
quality flicker and fluctuations meter in conformance with
EN61000-3-3 and EN61000-4-15.
A current measurement method can be used, as an alternative to
voltage measurement, thus eliminating the need for a reference
impedance.
Flicker severity is measured in terms of Pst and Plt using
analysis periods as defined within the standard.
Simultaneously full analysis of voltage variations is performed,
including the calculation of the maximum value dmax, the
difference between steady states dc, and the change
characteristic d(t).
|
|
|
|
|
SPECIFICATIONS
MAINS ANALYSER
Measurement Circuit: Single Phase with standard mains connector.
Current Rating: 16A rms continuous, or national connector rating if lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Current Ranges: ±24mA pk to ±400A pk in fifteen 2:1 ranges.
Frequency Range: 45 - 66 Hz.
Shunt Resistance: 3mOhms.
Sampling Rate: 300 points per cycle.
Basic Accuracy: <0.2% ±1mA, up to 16A.
Measured Parameters: Vrms, Vpk, Arms, Apk, Crest factors, THD, W, VA,
Power factor, Frequency, Inrush current.
Monitor Outputs: Re-constructed Voltage and Current Signals.
HARMONICS ANALYSER
Measurements:1st harmonic to 40th harmonic.
Measurement processing for both 1995 and 2000 Editions of EN61000-3-2.
Continuous calculation, analysis and assessment of unfiltered, filtered,
average, minimum and maximum current harmonic levels and limits. Continuous
measurement and assessment of supply waveform and harmonics.
Current Rating: 16A rms continuous, or national connector rating if lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Current Ranges: ±24mA pk to ±400A pk in fifteen 2:1 ranges.
Frequency Range: 45 - 66 Hz.
Shunt Resistance: 3mOhms.
Transforms Window:Continuous 4, 10, 12 or 16 cycle Discrete Fourier
Transforms.
Basic Accuracy: Better than 5% of limit or 0.2% of selected range
whichever is the greater.
Display of load supply assessment for voltage, harmonics, crest limits and
frequency against requirements of EN61000-3-2. Histogram or tabular display of
supply voltage harmonics. Histogram display of current harmonics with limits,
Min. hold, Max. hold and percentage of limit display options.
Tabular display of current harmonics showing present values, limits, average
values, average as percent of limit, maximum values, maximum as percent of limit
and pass or fail assessment for each harmonic.
Test Control: Untimed, manually timed or automatically
timed tests; user-defined test time. Limits automatically determined from
EN61000-3-2 for appropriate class; Class C and Class D limits can be
automatically calculated from power measurements or from ratings declared by the
user. Minimum and maximum power thresholds for limits can be changed by the
user. Facility for declaring supply voltages other than 230V and deriving
appropriate limits. Facility for insetting test limits.
Report Printing: Direct printer connection for
hard-copy report with user-entered narrative, supply voltage assessment and
current harmonic analysis and assessment.
VOLTAGE FLUCTUATIONS & FLICKER METER
Measurement: Voltage fluctuations dmax, dc, d(t) and flicker Pst and Plt
to EN61000-3-3 and EN61000-4-5.
Current Rating: 16A rms continuous, or national connector rating if lower.
Voltage Ranges: 115V (±200V pk) 230V (±400V pk).
Fluctuation Range: 25% max. (relative to nominal
voltage)
Flickermeter Range: Voltage change up to 20% (sinewave
change) or 10% (low repetition rate rectangular change) relative to AGC level.
Equivalent to 6400 pu on 8.8 Hz sinewave.
Flickermeter AGC: Up to ± 5%.
Flickermeter Accuracy: Better than 5% for Pst range
0·7 to 10·0.
Frequency Range: 50 or 60 Hz (operates over 43 – 67
Hz).
Report Printing: Tabular listing of voltage
variations, Pst classifier and Pst in each Plt interval.
GENERAL
Display: 320 x 240 pixel backlit LCD.
Interfaces: Parallel Printer, RS-232, USB).
Instrument Supply: 230V or 115V ±14%, 48 to 65Hz.
Operating Range: +5°C to 40°C, 20-80% RH.
Storage Range: –10°C to +60°C.
Dimensions: 357 x 132 x 235mm (WxHxD)
Weight: 4.4kg
Safety: Complies with EN61010-1
EMC Compliance: Complies with EN61326-1
HA-PC LINK PLUS SOFTWARE
HA-PC LINK PLUS is PC (Windows) software supplied with the HA1600A. It can
communicate with the instrument through either an RS232 or a USB connection.
It is intended to assist users in taking routine compliance measurements and
archiving the results.
The PC is used for configuration, display and data archiving only; all real time
data handling and measurement processing continues to be performed by the
Digital Signal Processor in the instrument. The performance of the PC does not
affect the accuracy of the measurement results, and so there is no need for the
either the PC or its software to be covered by a calibration certificate.
|
Thurlby Thandar Instruments Ltd. operates a policy of continuous development
and reserves the right to alter specifications
without prior notice.
|
 |
|