Xantrex XT Series DC Power Supply - Specifications

  • Seven Models
  • Very low noise and ripple
  • Excellent line/load regulation
  • Fast transient response
  • Constant voltage, constant current
  • Digital displays plus analogue bargraph
  • Optional analogue programming (inc. OVP)
  • Optional internal 16-bit GPIB (IEEE-488) and RS-232 control
  • LabWindows® drivers
  • Front and rear connectors standard
  • Ten turn voltage and current setting
  • Remote sense
  • CE, CSA, approvals

Models

XT7-6 XT15-4 XT20-3 XT30-2 XT60-1 XT120-0.5 XT250-0.25
Output Ratings
Output Voltage
Output Current
Output Power
0-7 V
0-6 A
42 W
0-15 V
0-4 A
60 W
0-20 V
0-3 A
60 W
0-30 V
0-2 A
60 W
0-60 V
0-1 A
60 W
0-120 V
0-0.5 A
60 W
0-250 V
0-0.25 A
62.5 W
Line Regulation (1)
Voltage (0.01% of Vmax+2 mV
Current (0.01% of Imax+0.25 mA)
2.7 mV
0.85 mA
3.5 mV
0.65 mA
4 mV
0.55 mA
5 mV
0.45 mA
8 mV
0.35 m
14 mV
0.3 mA
27 mV
0.275 mA
Load Regulation (2)
Voltage (0.01% of Vmax+2 mV)
Current (0.01% of Imax+0.25 mA)
2.7 mV
0.85 mA
3.5 mV
0.65 mA
4 mV
0.55 mA
5 mV
0.45 mA
8 mV
0.35 mA
14 mV
0.3 mA
27 mV
0.275 mA
Meter Accuracy
Voltage (1% of Vmax+1 count)
Current (1% of Imax+1 count)
0.08 V
0.07 A
0.25 V
0.05 A
0.3 V
0.04 A
0.4 V
0.03 A
0.7 V
0.02 A
2.2 V
0.006 A
3.5 V
0.004 A
Output Noise & Ripple (Vmode) (20 Hz-20 MHz)
RMS:
Peak-to-Peak:
1 mV
2 mA
1 mV
2 mA
1 mV
2 mA
1 mV
2 mA
1 mV
2 mA
1 mV
2 mA
1 mV
2 mA
Stability (3)
Voltage (0.02% of Vmax)
Current (0.03% of Imax)
1.4 mV
1.8 mA
3 mV
1.2 mA
4 mV
0.9 mA
6 mV
0.6 mA
12 mV
0.3 mA
24 mV
0.15 mA
50 mV
0.075 mA
Temperature Coefficient (4)
Voltage (0.015% of Vmax/°C)
Current (0.02% of Imax/°C)
1.05 mV
1.2 mA
2.25 mV
0.8 mA
3 mV
0.6 mA
4.5 mV
0.4 mA
9 mV
0.2 mA
18 mV
0.1 mA
37 mV
0.05 mA
Specifications are warranted over a temperature range of 0-30°C with default local sensing. Above 30°C, derate output lineraly to zero at 70C.
(1) For input voltage variation over the AC input voltage range, with constant rated load.
(2) For 0-100% load variation, with constant nominal line voltage
(3) Maximum drift over 8 hours with constant line, load and temperature, after 30 minute warmup.
(4) Change in output per C change in ambient temperature, with constant line and load.

Operating Ambient Temperature:
0-30°C with default local sensing. Above 30°C, derate output linearly to zero at 7°C
Storage Temperature Range:
-55°C to +85°C
Humidity Range:
0 to 80% RH Non-condensing.
Front Panel Control:
10-turn voltage and one-turn current potentiometers (10-turn current control optional)
Front Panel Voltage Control Resolution:
0.02% of V max
Voltage Mode Transient Response Time:
<100 µs for output voltage to recover within 0.05% of previous level after step change in load current of up to 50% of rated output in the range of 25% to 100% or rated output.
AC Input:
104-127 Vac at 1.2 A rms, 57-63 Hz.
Maximum Voltage Difference from output to safety ground:
400 Vdc.
Agency Approvals:
CSA, CE
Specifications with optional RS-232/GPIB Interface:
GPIB - Internal GPIB Interface:
Full feature GPIB programming with 14-bit resolution and software calibration.
RS232 - Internal RS-232 Interface: Serial instrument programming using the RS-232 protocol.

Models

XT7-6 XT15-6 XT20-3 XT30-2 XT60-1 XT120-0.5 XT250-0.25
Program Resolution
Voltage
Current
OVP
1.1 mV
1.0 mA
1 mV
2.4 mV
0.6 mA
2.4 mV
3.1 mV
0.5 mA
3.1 mV
4.7 mV
0.3 mA
4.7 mV
9.3 mV
0.2 mA
9.3 mV
17 mV
0.1 mA
17 mV
39 mV
0.05 mA
39 mV
Program Accuracy
Voltage
.

Current
.

OVP

10 mV
±0.1%

110 mA
±0.15%

70 mV

20 mV
±0.1%

70 mA
±0.15%

150 mV

20 mV
±0.15%

50 mA
±0.15%

200 mV

30 mV
±0.15%

40 mA
±0.15%

300 mV

200 mV
±0.15%

260 mA
±0.15%

600 mV

400 mV
±0.15%

130 mA
±0.15%

1.2 V

800 mV
±0.15%

7 mA
±0.15%

2.4 V

Readback Resolution
Voltage
Current
1.1 mV
1.0 mA
2.4 mV
0.6 mA
3.1 mV
0.5 mA
4.7 mV
0.3 mA
9.3 mV
0.2 mA
17 mV
0.1 mA
36 mV
0.05 mA
Readback Accuracy
Voltage
.

Current
.

10 mV
±0.15%

110 mA
±0.15%

10 mV
±0.1%

70 mA
±0.15%

10 mV
±0.1%

50 mA
±0.15%

15 mV
±0.1%

40 mA
±0.15%

35 mV
±0.15%

26 mA
±0.2%

70 mV
±0.3%

13 mA
±0.2%

150 mV
±0.3%

7 mA
±0.2%

Specifications with optional APG Analog Programming Interface

APG - Internal Analog Programming Interface: Includes overvoltage protection (OVP), remote ON/OFF, master slave tracking.

Remote Programming: 0-10 V or 0-10 kilohms = 0 to 100% of output voltage & current
Remote ON/OFF: TTL compatible, selectable logic high or low
Overvoltage Protection: Adjustable 3 V to Vmax +10%
Master/Slave Tracking: Within 1%
Output Fail Flag: Logic Low = Active

Thurlby Thandar Instruments Ltd.   Glebe Road, Huntingdon, Cambridgeshire PE29 7DR  U.K.
Tel: 01480 412451  Fax: 01480 450409  Email: sales@tti.co.uk   
Web: http://www.tti.co.uk