| | | Xantrex XKW Series Power Supplies - Specifications | | | | | Xantrex's XKW Series is available in nineteen 1000 watt and 3000 watt models. Jump to 3 kW Specs. >> | | | | Specifications (1) for the XKW 1kW Series (Specifications are subject to change without notice.) | | Model | XKW 8-125 | XKW 20-50 | XKW 33-33 | XKW 40-25 | XKW 60-18 | XKW 80-13 | XKW 150-7 | XKW 300-3.5 | XKW 600-1.7 | | Output Ratings: | | Output Voltage | 0-8V | 0-20V | 0-33V | 0-40V | 0-60V | 0-80V | 0-150V | 0-300V | 0-600V | | Output Current | 0-125A | 0-50A | 0-33A | 0-25A | 0-18A | 0-13A | 0-7A | 0-3.5A | 0-1.7A | | Output Power | 1000W | 1000W | 1000W | 1000W | 1080W | 1040W | 1050W | 1050W | 1020W | | Line Regulation: (2) | | Voltage | 1mV | 1.5mV | 1.5mV | 3mV | 3mV | 3mV | 5mV | 10mV | 20mV | | Current | 10mA | 5mA | 3mA | 2mA | 2mA | 2mA | 1mA | 1mA | 1mA | | Load Regulation: (3) | | Voltage | 3mV | 3mV | 3mV | 5mV | 5mV | 5mV | 5mV | 10mV | 20mV | | Current | 20mA | 5mA | 5mA | 5mA | 5mA | 5mA | 5mA | 2mA | 1mA | | Meter Accuracy: | Voltage (0.5% of Vmax+1 count) | 0.05V | 0.2V | 0.3V | 0.4V | 0.4V | 0.5V | 0.9V | 3V | 4V | Current (0.5% of Imax+1 count) | 0.7A | 0.4A | 0.3A | 0.2A | 0.1A | 0.08A | 0.05A | 0.03A | 0.01A | | Output Noise & Ripple: | | Voltage rms | 7.5mv | 5mv | 5mv | 5mv | 5mv | 5mv | 15mv | 15mv | 75mV | | Voltage p-p (0-20MHz-20MHz) | 60mV | 60mV | 60mV | 60mV | 60mV | 60mV | 175mV | 175mV | 500mV | | Drift (8 hours): (4) | Voltage (0.05% of Vmax) | 4mV | 10mV | 16.5mV | 20mV | 30mV | 40mV | 75mV | 150mV | 300mV | Current (0.05% of Imax) | 62.5mA | 25mA | 16.5mA | 12.5mA | 9mA | 6.5mA | 3.5mA | 1.75mA | 0.85mA | | Temperature Coefficient: (5) | Voltage (0.02% of Vmax/°C) | 1.6mV | 4mV | 6.6mV | 8mV | 12mV | 16mV | 30mV | 60mV | 120mV | Current (0.03% of Imax/°C) | 37.5mA | 15mA | 9.9mV | 7.5mA | 5.4mA | 3.9mA | 2.1mA | 1.05mA | 0.51mA | | OVP Adjustment Range: | | (5% to 110% of Vmax) | 0.4 - 8.8V | 1 - 22V | 1.65 - 36.3V | 2 - 44V | 3 - 66V | 4 - 88V | 7.5 - 165V | 15 - 330V | 30 - 660V | | Efficiency: (8) | | | 80% | 82% | 84% | 84% | 84% | 84% | 84% | 87% | 86% | (1) Specifications indicate typical performance at 25°C ±5°C, nominal line input of 120VAC. (2) For input voltage variation over the AC input voltage range, with constant rated load. (3) For 0-100% load variation, with constant nominal line voltage. (4) Measured at full rated output with a resistive load. (5) Maximum drift over 8 hours with constant line, load, and temperature, after 30-minute warm-up. | | GPIB Interface Specifications (with optional interface installed) | | Model | XKW 8-125 | XKW 20-50 | XKW 33-33 | XKW 40-25 | XKW 60-18 | XKW 80-13 | XKW 150-7 | XKW 300-3.5 | XKW 600-1.7 | | Program Resolution (16 Bit) | | Voltage (mV) | 2.4 | 6 | 9.9 | 12 | 18 | 24 | 45 | 90 | 180 | | Current (mA) | 37.5 | 15 | 9.9 | 7.5 | 5.4 | 3.9 | 2.1 | 1.05 | 0.51 | | OVP (mV) | 4 | 10 | 16.5 | 20 | 30 | 40 | 75 | 150 | 300 | | Program Accuracy | | Voltage (mV) | 30 | 75 | 75 | 75 | 150 | 150 | 300 | 300 | 750 | | Current (mA) | 500 | 250 | 200 | 140 | 120 | 80 | 40 | 20 | 20 | | OVP (mV) | 80 | 200 | 330 | 400 | 600 | 800 | 1500 | 3000 | 6000 | | Readback Resolution (16 Bit) | | Voltage (mV) | 2.4 | 6 | 9.9 | 12 | 18 | 24 | 45 | 90 | 180 | | Current (mA) | 37.5 | 15 | 9.9 | 7.5 | 5.4 | 3.9 | 2.1 | 1.05 | 0.51 | | Readback Accuracy | | Voltage (mV) | 30 | 75 | 75 | 75 | 150 | 150 | 300 | 300 | 750 | | Current (mA) | 500 | 250 | 200 | 140 | 120 | 80 | 40 | 20 | 20 | | XKW 1kW General Specifications | | Operational AC Input Voltage | 200-250 VAC at 10 Arms 1f, or 100-130 VAC at 20 Arm 1f, 47-63Hz | | Switching Frequency | Nominal 100 kHz, 200 kHz output ripple (>80 V models=80kHz, 160 kHz output ripple) | | Time Delay | 2 s maximum from power on until output stable | | Voltage Mode Transient Response Time | <1 ms recovery to 1% band for 30% step load change from 70% to 100% or 100% to 70% | | Maximum Voltage Differential | ±600 VDC from output to safety ground | | Remote Start/Stop and Interlock | TTL-compatible input; Contact Closure 12-250 VAC or 12-130 VDC | | Remote Analog Programming | Voltage and current programming inputs (source must be isolated): 0-5 k resistances; 0-5 V (default), 0-10 V voltage sources' 0-1 mA sources. OVP programming 0-5, 0-10 V voltage sources | | Remote Analog Monitoring | Output voltage and current: 0-5 V. Zero to full scale output 1% accuracy | | Maximum Remote Sense Line Drop Compensation | 1 V/line (line drop is subtracted from total voltage available at supply output) | | Operating Temp. Range | 0 to 50°C | | Storage Temperature Range | -55 to 85°C | | Humidity Range | 0 to 80% RH, non-condensing | | Front Panel Voltage and Current Control | 10-turn voltage and current potentiometers | | AC Input Connector Type | Barrier strip #6 screw with cover | | Main Output Connector | Nickel-plated copper bus bars | | Weight | Approximately 8.2 kg (18 lb) | | Approvals | CE-marked units comply with the general protection requirements of the European EMC directive, 89/.336/EEC: EN55011 Group 1, Class A, EN50081-2, EN50082-1 and with the European LV Directive 72/23/EEC: IEC 1010-1, IEC 1010-2 CSA certified | | XKW 1kW Options | | GPIB-XKW1 | GPIB Interface Card | | ISOL-XKW1 | Isolated Interface Card provides isolated analog control and readback of output voltage or current | | M13 | Locking Bushings on front panel controls | | 3KW Series | | | Specifications(1) for the XKW 3kW Series (Specifications are subject to change without notice) | | | Model | XKW 8-350 | XKW 10-300 | XKW 12-250 | XKW 20-150 | XKW 40-75 | XKW 55-55 | XKW 60-50 | XKW 80-37 | XKW 150-20 | XKW 300-10 | | Output Ratings: | | | Output Voltage | 0-8V | 0-10V | 0-12V | 0-20V | 0-40V | 0-55V | 0-60V | 0-80V | 0-150V | 0-300V | | Output Current | 0-350A | 0-300A | 0-250A | 0-150A | 0-75A | 0-55A | 0-50A | 0-37A | 0-20A | 0-10A | | Output Power | 2800W | 3000W | 3000W | 3000W | 3000W | 3025W | 3000W | 2960W | 3000W | 3000W | | Line Regulation: (2) | | | Voltage | 2mV | 2mV | 2mV | 2mV | 2mV | 2mV | 2mV | 2mV | 7.5mV | 15mV | | Current | 15mA | 15mA | 15mA | 15mA | 5mA | 2mA | 2mA | 2mA | 2mA | 2mA | | Load Regulation: (3) | | | Voltage | 5mV | 5mV | 5mV | 5mV | 5mV | 5mV | 5mV | 5mV | 15mV | 15mV | | Current | 15mA | 15mA | 15mA | 15mA | 5mA | 5mA | 5mA | 5mA | 5mA | 5mA | | Meter Accuracy: | | Voltage (0.5% of Vmax + 1 count) | 0.05V | 0.06V | 0.07V | 0.2V | 0.3V | 0.4V | 0.4V | 0.5V | 0.9V | 3V | Current (0.5% of Imax + 1 count) | 3A | 3A | 2A | 0.9A | 0.5A | 0.4A | 0.4A | 0.3A | 0.2A | 0.06A | | Output Noise & Ripple: | | | Voltage rms | 10mV | 12mV | 12mV | 12mV | 15mV | 15mV | 15mV | 15mV | 20mV | 20mV | Voltage p-p (0-20MHz-20MHz) | 90mV | 90mV | 90mV | 90mV | 100mV | 100mV | 100mV | 150mV | 150mV | 200mV | | Analog Prog. Accuracy | | Voltage (1% of Vmax) | 80mV | 100mV | 120mV | 200mV | 400mV | 550mV | 600mV | 800mV | 1.5V | 3V | | Current (1% of Imax) | 3500mA | 3000mA | 2500mA | 1500mA | 750mA | 550mA | 500mA | 370mA | 200mA | 100mA | | Drift (8 hours): (4) | | Voltage (0.05% of Vmax) | 4mV | 5mV | 6mV | 10mV | 20mV | 27.5mV | 30mV | 40mV | 75mV | 150mV | Current (0.05% of Imax) | 175mA | 150mA | 125mA | 75mA | 37.5mA | 27.5A | 25mA | 18.5mA | 10mA | 5mA | | Temperature Coefficient: (5) | | Voltage (0.02% of Vmax/°C) | 1.6mV | 2mV | 2.4mV | 4mV | 8mV | 11mV | 12mV | 16mV | 30mV | 60mV | Current (0.03% of Imax/°C) | 105mA | 90mA | 75mA | 45mA | 22.5mA | 16.5mA | 15mA | 11.1mA | 6mA | 3mA | | OVP Adjustment Range: | | | (5% to 110% of Vmax) | 0.4 - 8.8V | 0.5 - 11V | 0.6 - 13.2V | 1 - 22V | 2 - 44V | 2.75 - 60.5V | 3 - 66V | 4 - 88V | 7.5 - 165V | 15 - 330V | (1) Specifications indicate typical performance at 25°C ± 5°C, nominal line input of 208VAC. (2) For input voltage variation over the AC input voltage range, with constant rated load. (3) For 0-100% load variation, with constant nominal line voltage. (4) Maximum drift over 8 hours with constant line, load, and temperature, after 30-minute warm-up. (5) Change in output per °C change in ambient temperature, with constant line and load. | | | GPIB Interface Specifications (with optional interface installed) | | | Model | XKW 8-350 | XKW 10-300 | XKW 12-250 | XKW 20-150 | XKW 40-75 | XKW 55-55 | XKW 60-50 | XKW 80-37 | XKW 150-20 | XKW 300-10 | | Program Resolution (16 Bit) | | | Voltage (mV) | 2.4 | 3 | 3.6 | 6 | 12 | 16.5 | 18 | 24 | 45 | 90 | | Current (mA) | 105 | 90 | 75 | 45 | 22.5 | 16.5 | 15 | 11.1 | 6.5 | 3.3 | | OVP (mV) | 4 | 5 | 6 | 10 | 20 | 27.5 | 30 | 40 | 75 | 150 | | Program Accuracy | | | Voltage (mV) | 50 | 50 | 50 | 50 | 50 | 75 | 75 | 100 | 180 | 360 | | Current (mA) | 800 | 390 | 330 | 200 | 100 | 75 | 70 | 50 | 50 | 50 | | OVP (mV) | 80 | 100 | 120 | 200 | 400 | 550 | 600 | 800 | 1500 | 3000 | | Readback Resolution (16 Bit) | | | Voltage (mV) | 2.4 | 3 | 3.6 | 6 | 12 | 16.5 | 18 | 24 | 45 | 90 | | Current (mA) | 105 | 90 | 75 | 45 | 22.5 | 16.5 | 15 | 11.1 | 6.65 | 3.3 | | Readback Accuracy | | | Voltage (mV) | 75 | 75 | 75 | 75 | 75 | 100 | 110 | 150 | 280 | 560 | | Current (mA) | 900 | 750 | 600 | 300 | 200 | 150 | 135 | 100 | 100 | 100 | | XKW 3kW General Specifications | | Operational AC Input Voltage | 200-250 VAC at 26 Arms 1ø, or 190-250 VAC at 16 Arms 3ø, 47-63 Hz | | Switching Frequency | Nominal 30 kHz (60 kHz output ripple) | | Time Delay | 5s maximum from power on until output stable | | Voltage Mode Transient Response Time | <1 ms recovery to 1% band for 30% step load change from 70% to 100% or 100% to 70% | | Maximum Voltage Differential | ±400 VDC from output to safety ground | | Remote Start/Stop and Interlock | TTL-compatible input; Contact Closure 12-250 VAC or 12-130 VDC | | Remote Analog Programming | Voltage and current programming inputs (source must be isolated): 0-5 k resistances; 0-5 V (default), 0-10 V voltage sources; 0-1 mA sources. OVP programming 0-5 V, 0-10 V voltage sources | | Remote Analog Monitoring | Output voltage and current: 0-5 V, 0-10 V. 0 to full scale output 1% accuracy | | Maximum Remote Sense Line Drop Compensation | 1V/line (Line drop is subtracted from total voltage available at supply output) | | Operating Temperature Range | 0 to 50°C | | Storage Temperature Range | -55 to 85°C | | Humidity Range | 0 to 80% RH, non-condensing | | Front Panel Voltage and Current Control | 10-turn voltage and current potentiometers | | AC Input Connector Type | Chassis-Mounted Parts: Housing AMP 641685-1; Contact pins AMP 35082-1 Mating Connector Parts: Housing AMP 643267-2; Contact pins AMP 350821-1 | | Main Output Connector | Nickel-plated copper bus bars | | Weight (one unit) | Approximately 16kg (35 lb) | | Approvals | CE-marked units comply with the general protection requirements of the European EMC Directive, 89/336/EEC: EN55011 Group 1, Class A, EN50081-2, EN50082-1 and with the European LV Directive 72/23/EEC: IEC 1010-1, IEC 1010-2. CSA certified | | XKW 3kW Options | | GPIB-XFR3 | GPIB Interface Card (16 Bit) | | ISOL-XFR3 | ISOL Interface card allows isolated programming of output voltage or current | | M13 | Locking Bushings on front panel controls | | SR-XKW3 | Output strain relief kit | | | | |  | Thurlby Thandar Instruments Ltd. Glebe Road, Huntingdon, Cambridgeshire PE29 7DR U.K. Tel: 01480 412451 Fax: 01480 450409 Email: sales@tti.co.uk Web: http://www.tti.co.uk | | | | |