Maximize Performance and Versatility and
Virtually Eliminate Downtime
Pacific's unique master/slave configuration allows up to
ten 62.5 kVA mainframes to be paralleled in the field. Any
mainframe may be designated as the master. A failed unit is
automatically disconnected from the power grid providing
unmatched mission reliability.
Pacific's MS-Series
Power Source Systems Feature
-
Maximum system reliability
-
Rugged, powerful output
-
Lower installation cost
-
All frequency operation
-
Lower maintenance cost
-
Facility/test power flexibility
-
Unmatched performance/price ratio
-
Simple display and diagnostics
-
Uninterruptible Power Source configuration (UMS Option)
readily available
True Advantages
Solid State Technology with Unmatched Price/Performance
Ratio
Pacific MS-Series is a family of High Performance
Line Conditioners/Frequency Converters that provides highly
flexible, yet reliable, AC power ranging from 62.5 to 625 kVA.
Using field-proven double conversion methods, the MS-Series
offers unmatched power quality without sacrificing size or
efficiency.
Input AC power is rectified to DC by a
special input power supply section. This minimizes input
current distortion and prevents the load power factor from
reflecting back onto the utility line. The DC is then
converted back to AC by a high frequency, solid state,
pulse-width modulated switchmode inverter under the control of
a highly stable digital oscillator. The result is exceptional
system performance with maximum reliability.
Rugged, Powerful Output
-
350 Amps of Pulse Current is delivered by each 3060-MS
for driving non-linear loads.This eliminates the need to
oversize power equirements as is common to rotary or low
quality PWM power systems.
-
Load Power Factor is not an issue. The 3060-MS will
drive virtually any load without damage or risk.
-
Excellent Regulation and response time eliminates load
cross talk. Voltage sags common to other conversion methods
are eliminated with 150 microsecond response time to a 50%
load step. The output recovers to ± 3% of nominal within
less than 1/10th of a cycle at 400 Hz.
Maximum Reliability
-
Each 3060-MS is capable of operating as either the
master or slave in a multi-cabinet parallel system.
Calculated single cabinet MTBF is greater than five years.
-
Mission Reliability is assured. The parallel system
architecture is such that a failed slave unit automatically
removes itself from the power grid. Should the master unit
fail, the operator can select any other paralleled unit as
the new master from the front panel and restore system
operation.
Low Cost Ownership
-
Lower Maintenance Costs are achieved through built-in
diagnostics that minimize MTTR. Quick and easy repair is
facilitated with a small complement of local spares.
-
Input Power Factor is a constant 0.95 lagging,
regardless of load. The MS Series actually corrects PF
reflected back to the utility, eliminating PF penalties.
-
Low Installation Cost. The MS Series fits through
standard doorways. Audible noise is limited to cooling fans.
There is no 400 Hz whine that requires noise isolation.
Solid state design with a forklift base eliminates the need
for concrete pads and vibration isolators common to rotary
installations.
Facility/Test Power Flexibility
-
Power Levels Grow with demand. Units may be added or
removed from the power grid as required.
-
Variable Frequency range of 47-500 Hz, as well as switch
selectable fixed frequency operation of 50, 60 or 400 Hz is
standard on every model (800Hz optional contact factory for
more information).
-
External Input is provided as a standard feature. This
allows operation as a variable frequency test power
amplifier.
-
UPC-32 Programmable Controller Option is available to
provide steady state and transient control of output power
from the RS-232 or GPIB bus.
Simple/Informative Display
-
Measures volts, amps, watts and kVA for each input and
output phase.
-
Efficiency is continuously monitored allowing system
performance verification.
-
Internal Diagnostics assist in quickly locating failed
components resulting in extremely low MTTR.
-
Power Generation circuits are separate from display and
diagnostics. A failure in the display logic will not affect
output power quality. Output power cannot be interrupted by
system interrogation.
-
Audible and Visual Alarms alert the operator to any
conditions requiring attention.
The 3060-MS Delivers High Quality AC Power for
all Applications
Electrical Specifications
Output
Power: 62.5kVA/50kW for each
3060-MS.
Voltage: 0-120/208, 3 phase. May be
loaded either WYE or Delta. Other voltages are available as an
option.
Current: 175 Arms per phase continuous.
350Apk per phase for non-linear loads.
Load Transient Response and Recovery
Time: 150 microseconds for 50% load step and 300
microseconds for 100% load step.
Load Power
Factor: Any. Unit delivers full rated kVA into any
power factor.
Load Balance
Restrictions: None. Each phase is independently
regulated.
Isolation: Input is
fully isolated from output and frame
ground.
Protection: Integral
electronic current limiting with auto recovery. Output CB
optional.
Input
Voltage: Universal input transformer
with provisions for 208, 240, 380 and 480VAC, 3 phase +
10%.
Frequency: 47-63 Hz.
Physical
Specifications
Size: 36"W x
30"D x 72"H (see
diagram).
Weight: 1600 lbs.,
Approximately 1700 lbs. shipping
weight.
Efficiency: 85 to 90%.

Additional Features
-
Run time meter.
-
Auto restart.
-
RS-232 serial port for remote monitoring and
diagnostics.
-
Programmable voltage & frequency alarm set points.
-
Local automatic gain control. Remote sense optional.
-
ETL Listing (optional on standard MS-Series cabinet
only).
-
CE Mark (optional on standard MS-Series cabinet).
UMS Option
MS Series Battery Support Systems
The battery support system for a single cabinet UMS
installation (62.5kVA, 50kW) consists of 30 sealed,
maintenance free, immobilized electrolyte, batteries installed
in an open battery rack. The UMS system DC voltage regulator
provides for automatic charging of the battery system to
maintain the proper float voltage.
A battery disconnect center is located on the end of the
battery rack.
Battery support time at full load (50kW) is approximately
15 minutes. The waveform quality at the end of the battery
support time meets the requirements of MIL-STD 1399, section
300A, Types I, II and III power forms.
On-Line, No-Risk Battery Test
This feature of the UMS system provides the ability to
perform a battery test on command from the front panel or
RS-232 serial port. Test results are displayed on the front
panel and are available over the serial port as a part of the
system diagnostics. A battery failure during the test will not
cause the system to drop the load or distort the output
waveform.
Specifications are subject to change without
notice.
|