 | The Fluke Handheld Test Tools range is available from TTid in the UK | | | Fluke 43 Power Quality Analyser - Specifications | | | | | - Voltage, current, and power harmonics
- Up to 51st harmonic
- Total harmonic distortion (THD)
- Phase angle of individual harmonics
- Watts, power factor, displacement power factor, VA and VAR
- Voltage and current waveforms
- Continuously measure volts and amps on a cycle-by-cycle basis for up to
16 days | | | | Power | Line voltage adapter/battery charger included | | Installed battery | Rechargeable Ni-Cd pack | | Operating time | 4 hours | | Charging time | 4 hours | | Environmental | | Temperature | 0°C to 50°C (32°F to 122°F) | | Environmental | MIL 28800E, Type 3, Class III, Style B | | Enclosure | IP51 (dust, drip water proof) | | Mechanical Data | | Size: (H x W x D) | 232 x 115 x 50 mm (9.1 x 4.5 x 2 inches) | | Weight | 1.1 kg (2.5 lbs.) | | Safety | | Surge protection | 6 kV on input A and | | Floating measurements | 600V rms from any terminal to ground | | Warranty | 3 years parts and labor on Fluke 43, 1 year on accessories | | Technical Data | | Input Characteristics | | Input impedance | 1 MOhm, 20 pF | | Voltage Rating | 600V rms, CAT III | | Volt/Amps/Hertz Display | | True-rms voltage (ac+dc) | Ranges: 5.000V, 50.00V, 500.0V, 1250V* Accuracy: ±(1% +10 counts) | | True-rms current (ac + dc) | Ranges: 50.00A, 500.0A, 5.000 kA, 50.00 kA Accuracy: ±(1% +10 counts) | | Mains frequency | Ranges: 40.0 to 70.0 Hz Accuracy: ±(0.5% +2 counts) | | Power Display | | Watts, VA, VAR | Ranges: 250 W, 2.50 kW, 25.0 kW, 250 kW, 2.50 MW, 250 MW Accuracy: ±(4% +4 counts) | Power Factor, PF Displacement Power Factor, DPF | Range: 0.00 to 0.25 Accuracy: Not specified Range: 0.25 to 1.0 Accuracy: ±0.04 | | Harmonics Display | | Voltage | Ranges: 1st to 51st harmonic Accuracy: ±(3% +2 counts) to ±(15% +5 counts) | | Current | Ranges: 1st to 51st harmonic Accuracy: ±(3% +8 counts) to ±(5% +8 counts) | | Power | Ranges: 1st to 51st harmonic Accuracy: ±(5% +2 counts) to ±(30% +5 counts) | | Line frequency | Ranges: 40 Hz to 70 Hz fundamental Accuracy: ±0.25 Hz | | Phase | Ranges: 2nd to 51st harmonic Accuracy: ±3 ° to ±15 ° | | K-factor | Ranges: 1.0 to 30.0 Accuracy: ±10% | | Sags and Swells Recording | | Recording times | 4 min to 16 days (selectable) | | True-rms voltage | Ranges: 5.000V, 50.00V, 500.0V, 1250V* Accuracy: ±(2% +10 counts) | | True-rms current | Ranges: 50.00A, 500.0A, 5.000 kA, 50.00 kA Accuracy: ±(2% +10 counts) | | Other Recording | | Recording times | 4 min to 16 days (selectable) | | Parameters | | V/A/Hz | Line voltage, current, frequency | | Power | Watts, VA, VAR, PF, DPF, frequency | | Harmonics | THD, harmonic voltage, (or current, or power), frequency, % of total, phase | | Ohms | Ohms, diode, continuity, capacitance | | Temperature | Temperature | | Scope | DC voltage, dc current, ac voltage, ac current, frequency, pulse width, phase, duty cycle, peak max, peak min, peak min-max, crest factor | | Transient Capture | | Minimum pulse width | 40 ns | | Voltage threshold settings | 20%, 50%, 100%, 200% above or below normal voltage | | Min voltage and max voltage at cursor | Ranges: 10V, 25V, 50V, 125V, 250V, 500V, 1250V Accuracy: ±5% of full scale | | Inrush Capture | | Current ranges | Ranges: 1A, 5A, 10A, 50A, 100A, 500A, 1000A | | Inrush times | Ranges: 1s, 5s, 10s, 50s, 100s, 5 min | | Cursor readings, Current at cursor | Ranges: 12.5A, 25A, 50A, 125A, 250A, 500A, 1250A, 2500A, 5 kA Accuracy: ±5% of full scale | | Time between cursors | Ranges: 4 to 235 pixels (1 pixel = inrush time/250) Accuracy: ±(0.2% + 2 pixels) | | Scope Display | | Time ranges | Ranges: 20 ns/div to 60 s/div | | Max sampling rate | Ranges: 25 MS/s | | Bandwidth | Voltage channel [1]: 20 MHz at inputs, 1 MHz with TL24 Leads Current channel [2]: 15 kHz at inputs, 10 kHz with 80i-500s Probe | | Coupling | AC, DC | | Vertical sensitivity | Ranges: 5 mV/div to 500V/div | | Vertical resolution | 8 bit (256 levels) | | Record length | 512 samples per channel | | Timebase modes | Normal, roll, single | | Pre-trigger | Up to 10 divisions | | Measurements | dc, ac, ac+dc, peak, peak-peak, frequency, duty cycle, phase, pulse width, crest factor | | Ohms, Diode,Continuity | | Ohms | Ranges: 500.0W, 5.000 kW, 50.00 kW, 500.0 kW, 5.000 MW, 30.00 MW Accuracy: ±(0.6% +5 counts) | | Diode voltage | Accuracy: ±(2% +5 counts) | | Continuity | Beeper on at < (30W ±5W) | | Max current | 0.5 mA | | Capacitance | Ranges: 50.00 nF, 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF Accuracy: ±(2% +10 counts) | | Temperature** | Ranges: -100.0 °C to 400.0 °C, -200.0 °F to 800.0 °F Accuracy: ±(0.5% +5 counts) | | Screen Memories | 10 | | Optically Isolated RS-232 Interface | To printer: Supports HP LaserJet, DeskJet, Epson FX/LQ and Postscript printers with optional PAC91 Printer Adapter Cable To PC: FlukeView Power Quality Analyzer Software included | | FlukeView Power Quality Software | Hardware requirements: PC or 100% compatible with Windows 3.1, Windows 95, or Windows NT. Enough RAM for Windows operating system. 4 MB hard drive space. Pointing device (mouse) recommended. | | | | |  | Thurlby Thandar Instruments Ltd. Glebe Road, Huntingdon, Cambridgeshire PE29 7DR U.K. Tel: 01480 412451 Fax: 01480 450409 Email: info@ttid.co.uk Web: http://www.ttid.co.uk | | | |
|